Description
Slam Sut-off valve is installed immediately after the filter & prior to the Regulator. It normally remains open, incase the outlet pressure of the regulator exceeds the permissible limits, the slam shut off valve senses it through the impulse line & immediately shuts off the flow to downstream.When theregulatorisrepaired,theslamshutoffvalveistobeopenmanuallybypullingtheknob.Oncetheflowstartsthroughthe slam shut off valve it will remain open till the outlet pressure of the regulator is within limits.
Working Pressure 0.5 – 19 kg/cm²
Flow Rate 100 Scm3/hr
Shut Off Pressure Setting 0.05 – 0.5 bar. Also available from 0.5 – 5 bar
End Connection 4321 1” BSP Female, 4325 1” flanged
Medium LPG, Natural Gas, Oxygen, Nitrogen, Carbon dioxide, Air
Available in Self sensing & External sensing.
Will be supplied for assembly in gas train only.